Alarm Systems Inspection Annual fire alarm inspection of 400+ sensors, 60-70 pulls and strobes. All test requiring loud alarms must be done before opening. Please arrive at 7 am. All other tests that can be put on test and won't be loud can be done at anytime during their business hours.
Bert P.
Annual portable extinguisher inspection BRC ID: 137983 Emergency Light Inspection (6) Bug-eye lights Portable Extinguishers and Emergency / Exit Lights Inspection
Paul T.
Deliver (30) 5lb ABC Extinguishers Deliver (50) 3 hole wall hangers
Paul T.
Paul T.
Portable Extinguishers Service Call
Paul T.
Monthly Extinguisher Inspection BRC ID: 405727 Get with Chris Caulley so he can show you the suppression system for the metal blasting shop. Cameron will probably have to survey this at a later date.
Paul T.
Monthly Extinguisher Inspection BRC ID: 405727
Kenneth Y.
Annual Extinguisher Inspection
Paul T.
Monthly Extinguisher Inspection BRC ID: 405727
Bert P.
Alarm Systems Inspection Annual fire alarm inspection of 400+ sensors, 60-70 pulls and strobes. All test requiring loud alarms must be done before opening. Please arrive at 7 am. All other tests that can be put on test and won't be loud can be done at anytime during their business hours. Inoperable Deficiency: Upon inspection the FACP had multiple troubles. Had “Addr Loop on Line Loop 1-4” Troubles Prior Inspection. Also had multiple zones disabled zones 1-3 to be exact. After several trouble shooting attempts the panel was able to be normal. Periodically the FACP would go from normal to multiple loop troubles, 14 to be exact. I observed this for approximately an hour. After final conclusion the panel did stay normal. Also none of the strobes functioned after alarm was activated, with everything enabled. I checked the VEC panel and worked while I spoke into the mic. But no flashes nor sounds would come out during fire alarm activation.
Paul T.
Portable Extinguishers Inspection
Bobby H.
Annual Extinguisher Inspection
Bobby H.
Semi-Annual Kitchen System Inspection - 2 Hoods
Luis M.
Arrived on site Power Supply 4 ground fault. Ground fault was on NAC 1started troubleshooting found it on a ceiling mount device. Also went to the maintenance building and cleared a micro fault on power supply.
Justin S.
Portable Extinguishers Inspection
Troy L.
Replaced broken Simplex smoke/heat detector
Chris B.
Troubleshot panel to determine what is causing false alarms. Smoke detector is faulty and needs to be replaced.
Bobby H.
Conducted semi-annual kitchen hood inspection
Bert P.
q
Cameron R.
Semi-annual kitchen hood inspection. Installation of new caps on hood nozzles
Bert P.
Annual sprinkler inspection
Chris B.
Annual sprinkler inspection
Brett H.
Annual fire extinguisher inspection